接地及接地系統(tǒng)的安裝


DCS系統(tǒng)對(duì)接地要求較高,一般分為:

  • 本質(zhì)接地

  • 系統(tǒng)直流工作接地

  • 交流電源的保護(hù)接地

  • 保護(hù)接地等

各類接地系統(tǒng)、各接地母線之間彼此絕緣。

各接地系統(tǒng)檢查無混線后方能與各自母線和接地極相連。

系統(tǒng)直流工作接地要求高,不同家系統(tǒng)要求不同,阻值一般不能超過1Ω,因此打接地極。

其他系統(tǒng)接地要求為接地電阻小于4Ω。

保護(hù)接地可以與全廠系統(tǒng)地網(wǎng)相連。

接線


1、 硬件設(shè)備之間的連接

這種連接在控制室內(nèi)部進(jìn)行,大多采用多芯屏蔽雙絞線或同軸電纜,用標(biāo)準(zhǔn)化的插件插接。

這些電纜稱為系統(tǒng)電纜,種類多,所以工作時(shí)要仔細(xì)、謹(jǐn)慎,不能插錯(cuò),并做好檢查工作。

 

2、 DCS系統(tǒng)和在線儀表的連接

這是控制室與現(xiàn)場(chǎng)儀表的連接,量大點(diǎn)多,一般會(huì)有兩種形式:

l  一根電纜從頭到底,也就是現(xiàn)場(chǎng)儀表或執(zhí)行機(jī)構(gòu)的兩芯電纜直接連到控制室DCS系統(tǒng)相應(yīng)的模件接線端子;

l  控制室通過多芯主電纜連接到現(xiàn)場(chǎng)點(diǎn)集中的地方,通過接線盒再分別用兩芯電纜與每個(gè)現(xiàn)場(chǎng)儀表或執(zhí)行機(jī)構(gòu)連接。

由于接線點(diǎn)數(shù)較多,每個(gè)點(diǎn)準(zhǔn)確無誤,牢固可靠,排列整齊、美觀。


英文產(chǎn)品詳細(xì)信息

Grounding and installation of Earthing system

The grounding requirements for DCS systems are relatively high, generally divided into:

Intrinsic safety grounding

System DC working grounding

Protective grounding of AC power supply

Safety protection grounding, etc

All kinds of Earthing system and grounding buses are insulated from each other.

Each Earthing system can be connected to its own bus and grounding electrode only after no mixed wires are checked.

The DC working grounding requirements of the system are the highest, and different systems have different requirements. The resistance value generally cannot exceed 1 Ω, so a grounding electrode must be installed.

The grounding requirement for other systems is that the grounding resistance is less than 4 Ω.

The safety protection grounding can be connected to the grounding network of the entire plant system.


connection


1. Connection between hardware devices


This type of connection is carried out inside the control room, mostly using multi-core shielded twisted pair or coaxial cables, with standardized plug-in connections.


These cables are called system cables and have a variety of types, so when working, it is necessary to be careful and cautious, never plug them in incorrectly, and do a good job of inspection.


2. Connection between DCS system and online instruments


This is the connection between the control room and on-site instruments, which has a large quantity and usually comes in two forms:


A cable is connected from the beginning to the bottom, that is, the two core cable of the on-site instrument or actuator is directly connected to the corresponding module wiring terminal of the DCS system in the control room;


The control room is connected to a centralized location on site through a multi-core main cable, and then connected to each on-site instrument or actuator through a junction box using two core cables.


Due to the large number of wiring points, each point must be accurate, firm, reliable, neatly arranged, and aesthetically pleasing.

免責(zé)聲明:

AMIKON我們銷售新產(chǎn)品和停產(chǎn)產(chǎn)品,獨(dú)立渠道購(gòu)買此類特色產(chǎn)品。阿米控不是本網(wǎng)站特色產(chǎn)品的授權(quán)分銷商、經(jīng)銷商或代表。本網(wǎng)站上使用的所有產(chǎn)品名稱/產(chǎn)品圖片、商標(biāo)、品牌和徽標(biāo)均為其各自所有者的財(cái)產(chǎn)。帶有這些名稱,圖片、商標(biāo)、品牌和徽標(biāo)的產(chǎn)品描述、描寫或銷售僅用于識(shí)別目的,并不表示與任何權(quán)利持有人有任何關(guān)聯(lián)或授權(quán)。

ABBHoneywellSiemens
DP620 3BHE300016R18C-TDILA1 51307141-1756DS1122-8AA
V17111-130 V17151-2108C-TDIL11 51306858-1756DS1124-8AA
CI680 3BSE007364R18C-TDIL01 51306856-1756DS1211-8AA
AI86-16 570871968C-TAOXB1 51307137-175聽6DS1213-8AA
MEM86-3*192 CMBMR38C-TAOXA1 51307135-1756DS1220-8AA
UC86-8CH 572758718C-TAOX61 51306981-1756DS1222-8BA
YPG110E YT204001-FD8C-TAOX51 51306983-1756DS1223-8AA




會(huì)員登錄

×

請(qǐng)輸入賬號(hào)

請(qǐng)輸入密碼

=

請(qǐng)輸驗(yàn)證碼

收藏該商鋪

X
該信息已收藏!
標(biāo)簽:
保存成功

(空格分隔,最多3個(gè),單個(gè)標(biāo)簽最多10個(gè)字符)

常用:

提示

X
您的留言已提交成功!我們將在第一時(shí)間回復(fù)您~
在線留言