MKVV國標(biāo)電纜MKVV22礦用控制電纜10*2.5
供應(yīng)MVV-3*2.5礦用塑料電力電纜MVV
型號 | 規(guī)格 | 導(dǎo)電線芯mm | zui大直流電阻20℃ | 載流量A | |||
銅芯Ω/km | 鍍錫銅芯Ω/km |
|
|
| |||
|
|
|
|
|
|
| |
3×2.5+1×1.5 | 49/0.2530/0.25 | 7.98 | 8.21 | 26 |
| ||
3×4+1×2.5 | 56/0.3049/0.25 | 4.95 | 5.09 | 34 |
| ||
3×6+1×4 | 84/0.3056/0.30 | 3.30 | 3.39 | 43 |
| ||
3×10+1×6 | 84/0.4084/0.30 | 1.91 | 1.95 | 63 |
| ||
3×16+1×6 | 126/0.4084/0.30 | 1.21 | 1.24 | 84 |
| ||
3×25+1×10 | 196/0.4084/0.40 | 0.780 | 0.795 | 115 |
| ||
3×35+1×10 | 276/0.4084/0.40 | 0.554 | 0.565 | 142 |
| ||
3×50+1×16 | 396/0.40126/0.40 | 0.386 | 0.393 | 176 |
| ||
3×70+1×25 | 360/0.50196/0.40 | 0.272 | 0.277 | 224 |
| ||
3×95+1×35 | 475/0.50276/0.40 | 0.206 | 0.210 | 273 |
| ||
3×120+1×35 | 600/0.50276/0.40 | 0.161 | 0.164 | 316 |
| ||
3×150+1×50 | 756/0.50396/0.40 | 0.129 | 0.132 | 454
|
|
(1)切斷起火電纜電源。電纜著火燃燒,無論何原因引起,都應(yīng)立即切斷電源,然后,根據(jù)電纜所經(jīng)過的路徑和特征,認(rèn)真檢查,找出電纜的故障點,同時應(yīng)迅速組織人員進(jìn)行撲救。
(2)電纜溝內(nèi)起火非故障電纜電源的切斷。當(dāng)電纜溝中的電纜起火燃燒時,如果與其同溝并排敷設(shè)的電纜有明顯的著火可能性,則應(yīng)將這些電纜的電源切斷。電纜若是分層排列,則首先將起火電纜上面的受熱電纜電源切斷,然后將與起火電纜并排的電纜電源切斷,zui后將起火電纜下面的電纜電源切斷。
(3)關(guān)閉電纜溝隔火門或堵死電纜溝兩端。當(dāng)電纜溝內(nèi)的電纜起火時,為了避免空氣流通,以利迅速滅火,應(yīng)將電纜溝的隔火門關(guān)閉或?qū)啥硕滤?,采用窒息的方法滅火?nbsp;
(4)做好撲滅電纜火災(zāi)時的人身防護(hù)。由于電纜起火燃燒會產(chǎn)生大量的濃煙和毒氣,撲滅電纜火災(zāi)時,撲救人員應(yīng)戴防毒面具。為防止撲救過程中的人身觸電,撲救人員還應(yīng)戴橡皮手套和穿上絕緣靴,若發(fā)現(xiàn)高壓電纜一相接地,撲救人員應(yīng)遵守:室內(nèi)不得進(jìn)入距故障點4m以內(nèi),室外不得進(jìn)入距故障點8m以內(nèi),以免跨步電壓及接觸電壓傷人。救護(hù)受傷人員不在此限,但應(yīng)采取防護(hù)措施。
(5)撲滅電纜火災(zāi)采用的滅火器材。撲滅電纜火災(zāi)應(yīng)采用滅火機(jī)滅火,如干粉滅火機(jī)、“1211”滅火機(jī)、二氧化碳滅火機(jī)等;也可使用干砂或黃土覆蓋;如果用水滅火,使用噴霧水槍;若火勢猛烈,又不可能采用其他方式撲救,待電源切斷后,可向電纜溝內(nèi)灌水,用水將故障封住滅火。
(6)撲救電纜火災(zāi)時,禁止用手直接觸摸電纜鋼鎧和移動電纜
MKVV國標(biāo)電纜MKVV22礦用控制電纜10*2.5